Contents
·
Illumination of
Emergency lights
·
Coverage
·
Frequency of Emergency Lights Verification:
PURPOSE:
- To cater the entire electrical
load of the emergency lights, emergency exit lights and fire alarm panel
in a balanced pattern with preset level of circuit protection.
- To provide uninterrupted power
source to power outlets at all emergency lights and fire panel.
- To provide minimum level of
lightings at all floors at times of total black out or during the
changeover to the generator set.
- To maintain optimum level of
lighting in offices area with reference to the external lighting level.
SCOPE:
- This SOP will be applicable for
all uninterrupted power supply (UPS) backup and maintenance in the textile
sector.
RESPONSIBILITY:
- Responsibility is imposed on the
electrical engineer/Officer and the electrician who conducts the
inspection, who have jointly inspected, then the Electrical Manager / HOD
who will make sure that the inspection is done properly.
How to Do:
- Officer along with electrician shall visit
at the location where ups are placed. Visually inspect equipment for loose
connection, burned insulation or any other sign of wear.
- In amid of inspection, tightening loose
terminal points, batteries terminals and connection to prevent any
unintended loss/harm.
- Uninterrupted power supply capacity rating
is 1000Watt with attached dry batteries as liquid batteries are sensitive
to orientation. Dry cell does not require keeping them upright.
- Individuals must understand the
requirement of NFPA 70E.At the time of UPS inspection occurs, technician
should place the system into bypass mode or transfer the load to other
source in order to check the emergency lights
- Authorized person check indication lights
of on load and off load to work properly.
- Ensure UPS’s that are required are
suitable for purpose and can be powered via three-pin plug.
- Clean and vacuum UPS equipment enclosure
before conducting inspection.
- Technician visit UPS control DB to make
sure smooth operation of breakers, magnetic contactor and relays. Then
switch main source breaker to off position. Relay will automatically take
UPS on backup mode.10Watt of emergency lights attached to that specific
UPS must be functioning /operational. If not, check faulty light with the
help of multi meter to measure voltage and current for possible
rectification. Replace with the new light would be preferable.
- Note down starting and ending time of UPS
back time to make sure required standard time should be above ninety
minutes.
- Ensure UPS’s are recorded on a
file and regular inspection as per manufacturer instructions, are
undertaken, with record kept.
- Notify Estate and facility of the
intention to install a UPS of above 1KW prior to meet requirement.
- Instruction is to be given by
officer to electrician wearing all PPE’s while corrective action plan to
ensure problem does not occur again.
The
emergency power backup of batteries should not be less than 90 minutes.
1.
Illumination of Emergency lights
- Emergency lights of 10w install on above
of every exit and emergency door.
- Place emergency light at the angle of 45
bearing angle in order to get maximum illumination.
- Emergency light Signs having
lower Lux Level should be replaced.
2.
Emergency light Type
- The Emergency light type which
is used in facility is LED Emergency light of 10w.
3.
Cleanliness
- Every Emergency light should be cleaned.
- Use stair to reach the light.
- Clean the emergency light using shiner and
cloth.
- Cleaning of the Emergency light
is important, because it decreases the lux and overall fruitful efficiency
of the lights.
4.
Coverage
- Emergency lighting system
- Emergency Exit
- Fire Alarm panel
Acceptance Criteria:
The
points measured shall not be less than, the
values standard values given in the table below.
|
Instrumentation |
URS(User requirement
Specification) |
|
Emergency Power Backup |
According to user demand (90 Minutes approx.) |
|
Illumination of Emergency light |
According
to user demand (900 Lumens approx.) |
|
Emergency light Type |
LED Emergency light (mostly 10watt) |
|
Cleanliness |
Dust Proof |
|
Erection |
According to facility Design for Emergency |
Standards being followed:
Emergency light standards being
followed in the facility.
- International Building Code (IBC), 2015
edition.
- NFPA 70: National Electrical Code (NEC),
2017 edition.
- NFPA 99: Health Care Facilities Code, 2015
edition.
- NFPA 101: Life Safety Code, 2015 edition.
- NFPA 110: Standard for Emergency and Standby Power
Systems, 2016 edition.
- NFPA 111: Standard on Stored Electrical Energy
Emergency and Standby Power Systems, 2016 edition.
- NFPA 70E
- NFPA 101
for emergency lighting
1.
Frequency of Emergency Lights
Verification:
Frequency for UPS
Verification is at least once in a month.
- To cater issues and concern in order to
smooth functioning of UPS.
- International Building Code (IBC), 2015
edition.
So that’s the reason why Emergency light Verification, inspection is performed after one month to fulfill the audit requirement.
Reviewed by Electrical Engineering World
on
March 26, 2024
Rating:

