1. PURPOSE:
This SOP outlines procedures for verifying exit sign boards. It details inspection steps and criteria for compliance. The SOP guides report writing on verification findings. It ensures adherence to safety standards. Proper documentation enhances overall building safety.
2. SCOPE:
This Standard Operating Procedure (SOP) outlines the systematic procedure for verifying exit signs in industrial settings. It ensures compliance with safety regulations and confirms the functionality of exit signage. By following this SOP, personnel can conduct thorough inspections and maintain a safe environment for occupants during emergencies.
3. How to Do:
3.1 Emergency Power Backup Time:
- Switch off the main supply so that the Exit Signs get energized by their built in battery system.
- Note down the starting time of emergency backup drill.
- Round the whole facility, to check each and every Exit sign is illuminated or not.
- Damaged or Broken Exit signs should be replaced or repaired.
- Note down the end time of emergency backup.
The emergency power backup should
not be less than 90 minutes.
3.2 Illumination of Exit Signs
- Place lux meter in front of the Exit Sign Board at a distance of 1 meter.
- Lux Sensor should be right in front of Exit Sign.
- Do measure the lux of every Sign Board using Lux meter by setting the meter at Range A as described in the SOP of LUX METER.
- The Lux level should not be less than 10 lux for every Exit Sign Board to fulfill the acceptance criteria of illumination.
- Exit Signs having lower Lux Level should be replaced.
Result: Lux of the every Exit Sign should
not be less than 10 lux.
3.3 Battery System
As
we know, Exit Sign Boards have their own built in battery system, so no need of
any emergency backup for Exit Sign Boards. Make sure the following points only:
- Switch off the main supply of the exit sign boards floor by floor and visit that floor.
- Start the inspection of facility.
- Built in battery system should be good enough to fulfill the demand of 90 minutes backup.
- The built in battery should not heat, in case of warming effect, replace that board.
3.4 Exit Sign Type
·
The
Exit Sign Type which are mostly used in facility are LED Type Exit Lamp of 6w.
3.5 Cleanliness
- Every Sign board should be cleaned.
- Use stair to reach the board.
- Clean the board using shiner and cloth.
- Cleaning of the Exit Sign Board is important, because it decreases the lux, efficiency of built in battery system and overall fruitful efficiency of the board.
3.6 Erection
- The Exit Signs are erected/installed in such a way that they direct towards the emergency pathway as per the demand of building safety inspection team.
- In case of wrong erection, do consult with the facility’s responsible personnel of Electrical department and accommodate the changes.
- The Exit Sign Board should be proper and tight to their fixed point, do tight the loose or tilted boards.
4. Frequency of Emergency Exit Signs Verification:
Frequency for Emergency Light
Verification is once in a month.
5. Monthly Emergency Exit Sign Board Report Format:
|
|
|||||||||
|
Division: |
|||||||||
|
|
|||||||||
|
Emergency Power Testing Report
For Exit Sign Board |
|||||||||
|
Date :- _________________
Division |
|||||||||
|
Sr. No. |
Location |
Start Time |
End Time |
Total Time |
Required |
Result |
CAP |
Remarks |
|
|
1 |
|
|
|
|
90 Minutes |
|
|
|
|
|
2 |
|
|
|
|
90 Minutes |
|
|
|
|
|
3 |
|
|
|
|
90 Minutes |
|
|
|
|
|
4 |
|
|
|
|
90 Minutes |
|
|
|
|
|
5 |
|
|
|
|
90 Minutes |
|
|
|
|
|
6 |
|
|
|
|
90 Minutes |
|
|
|
|
|
Inspected By: |
|||||||||
|
Name:____________ |
|||||||||
|
Code:____________ |
|||||||||
|
Designation:____________ |
_________ |
||||||||
|
Signature:_____________ |
Verified By |
||||||||
6. RESPONSIBILITY: